Savol: Men 8 km uzunlikdagi 220 kV kabelni sinab ko'rishim kerak. Menga qanday SR reytingi kerak?
A: 7 bosqichli o'lchamlarni belgilash tartibi: test talablarini aniqlang → C ni hisoblang → L ni baholang → f_res hisoblang → reytinglarni tekshiring → takrorlang → yakunlang.
Bosqichma-bosqich--kV - 220 kV kabel, 8 km:
1. IEC 60840: V_test=2.0 × 127 kV=254 kV. Davomiyligi 60 min.
2. C ≈ 8 km × 0,2 mkF/km=1.6 mF.
3. 3× 100 kV/2 A reaktorlarni parallel ravishda ko‘rib chiqaylik: L=26.7 H, f=24.4 Gts.
4. 254 kV kuchlanishdagi oqim: I=V × 2pf × C=6.9 A. Lekin 3×2A → 6A jami → OK EMAS.
5. 3× 100 kV/4 A reaktorlarga yangilang: jami I=12 A → OK. P_in=254×6,9/35=50 kVt.
6. Umumiy vazni: 3×450 kg + 200 + 150 + 100=~1800 kg.
Umumiy stsenariylar uchun o'lchamlar xulosasi:
|
Ssenariy |
V_test (kV) |
C (μF) |
f (Hz) |
Tavsiya etilgan tizim |
|
33 kV kabel, 3 km |
48 |
0.6 |
45 |
60 kV/2A ×1, 5 kVt |
|
110 kV kabel, 5 km |
160 |
1.0 |
24 |
200 kV/4A ×2, 20 kVt |
|
220 kV kabel, 8 km |
254 |
1.6 |
24 |
300 kV/4A ×3, 50 kVt |
|
400 kV kabel, 5 km |
330 |
1.0 |
48 |
400 kV/2A ×2, 25 kVt |
|
GIS 245 kV, 10 dona |
230 |
0.05 |
80 |
300 kV/1A ×2, 5 kVt |
|
Generator 100 MVA |
28 |
2.5 |
45 |
30 kV/5A, 10 kVt |
Muhim eslatmalar:
• Reaktor kuchlanish darajasidagi +20% marja . +30% joriy reytingdan.
• Agar P_in > 100 kVt bo'lsa, seksiyaviy sinovni ko'rib chiqing (ko'pchilik standartlarda ruxsat berilgan).
• Haqiqiy Q taxmin qilinganidan past bo‘lishi mumkin - konservativ rejalashtirish maydondagi nosozliklarni oldini oladi.